Omega Stud Sensor LV800 User Manual

Users Guide  
Shop online at  
omega.com  
For latest product manuals:  
omegamanual.info  
LV800 SERIES  
Capacitance Point Level Sensors  
 
LV8 0 0 S ER IE S  
This manual contains the information necessary to ensure a safe and  
successful installation. Please read and comply with the section on page  
9 of this manual pertaining to SAFETY. Doing so will ensure proper oper-  
ation of the equipment and the safety of all personnel.  
Before discarding shipping container, please inspect it thoroughly and  
verify that all parts ordered are accounted for. Sometimes smaller parts  
become stuck under carton flaps and other packaging materials.  
2
 
P RE - IN STALLATIO N CO N SI D ER ATION S  
Choosing a Location: (See Figure 2)  
1) Material Flow - When selecting a location for the LV800,  
choose a point in the vessel where the probe will be out of  
the direct flow of incoming and outgoing material to prevent  
any mechanical damage that may be caused by the pres-  
sure of the flow. The LV800 must be positioned at a point  
where incoming material will reach and cover the probe in its  
normal flow, and when receding, will flow away from the  
probe in an even manner. For best results, choose a posi-  
tion where a majority of the probe, not just the tip, will be  
covered. This is particularly important when detecting mate-  
rials with low relative dielectric constants and low product  
densities. The unit will not operate as a “tip sensitive”  
device. For extended length models, allow for at least 8 to  
12 inches (203-305 mm) of probe coverage. When sensing  
highly conductive materials, or those with a high dielectric  
constant, the LV800 can perform as a “tip sensitive” sensor.  
2) Vessel Contact - Select an area where the probe can not  
contact any internal structure elements of the vessel.  
3) Driven Shield Penetration - Select a location which  
ensures that the driven shield section protrudes into the ves-  
sel and is not recessed in the mounting neck.  
4) Multiple Probe Proximity - If more than one sensor is  
mounted in the vessel, do not place the sensors closer than  
18 inches (457 mm) from one another.  
Cover Removal: (See Figure 1)  
Before loosening the cover, loosen or remove the cover lock  
screw. Spanner slots are incorporated on the top of the cover  
which should be used to loosen the cover from the housing.  
Use a flat bar for initial loosening. DO NOT use a strap or chain  
type wrench. Keep hands clear of threads on the cover and  
housing to avoid contact with the thread lubricant.  
Figure 2  
Figure 1  
3
 
M E CHAN IC AL IN STA LLATIO N  
EL EC TR IC A L IN S TA LL ATI O N  
Standard, Food Grade and Stub Probe Mounting:  
(See Figures 3 & 4)  
1) Select a mounting location in accordance with the Pre-  
Factory Wiring:  
The LV800 probe wires are connected to the backside of the  
PCB. DO NOT alter this connection. Doing will likely cause  
improper operation of the sensor.  
Installation Recommendations.  
2) If using a welded fitting, cut a hole into the side/top of the  
vessel corresponding to the mounting connection (1-1/4”  
NPT or 3/4” NPT). If using a mounting plate, cut a 2-1/2 inch  
(64 mm) center hole and six 11/32 inch(9mm) mounting  
holes (for 5/16” bolts) on a 7 inch (178 mm)bolt circle. Use  
mounting plate as a template.  
3) Weld fitting or attach mounting plate to vessel wall.  
4) Insert probe through fitting. Do not use sealant tapes (e.g.  
Teflon tape) or putties. When using the 1-1/4” NPT  
connection, grease threads with anti-seize then thread unit  
tightly into place by gripping and rotating housing. When  
using the 3/4” NPT connection, thread unit tightly into place  
by gripping and rotating 15/16 inch (24 mm) wrench flats  
provided on fitting. Continuity between sensor mounting  
point and vessel wall must be maintained to assure proper  
probe operation.  
Permanently Connected Equipment:  
Disconnecting devices shall by included in the system installa-  
tion. In installations were multiple circuits are used (i.e. inde-  
pendent circuits for power input and output relay), individual  
disconnects are required. The disconnects shall be within  
close proximity of the equipment, accessible to operators, and  
marked appropriately as the disconnect for the associated cir-  
cuit. Assure the disconnect ratings are appropriately sized for  
the circuit protected (See Specifications).  
Circuit Separation:  
Two cable entry locations are provided to aid in maintaining  
separation of "hazardous live" (typically mains voltages such as  
115VAC and 230VAC) and limited circuits (typically control  
voltages less than 30Vrms or 42.4VDC). However, since the  
LV800 single wiring compartment can not absolutely protect  
against physical contact between multiple circuits, it is required  
that all wiring used must have an insulation rating of 300V min-  
imum, and a temperature rating of 80˚ C (176˚ F) minimum.  
DIMENSIONS ARE SHOWN IN INCHES WITH MILLIMETER EQUIVALENT IN BRACKETS  
Protective Earthing:  
Each LV800 is provided with a "protective conductor terminal"  
which shall be terminated to the local earth ground potential to  
eliminate shock hazard in the unlikely event of internal insula-  
tion breakdown. Select wire size that can carry in excess of the  
sum of all circuit's maximum amperage.  
Figure 3  
Figure 4  
4
 
Power Input: (See Figure5)  
2-Step Calibration- probe exposed to material  
1) While the probe is not covered with material, rotate “Sense  
Adjust” clockwise just until “Sense” (yellow) LED turns on.  
2) Permit the application material to cover the probe. While  
counting the number of revolutions, rotate “Sense  
Adjust” counter-clockwise until the “Sense” (yellow) LED  
turns off. Reposition “Sense Adjust” at the half way point  
between the LED on and LED off settings. (e.g. After insert-  
ing the probe into the material, if it takes 2 counter-clockwise  
turns of “Sense Adjust” for the “Sense” (yellow) LED to turn  
off, then “Sense Adjust” should be repositioned 1 clockwise  
turn.)  
The LV800 is designed to accept either 115VAC or 230VAC  
(factory set). Verify the intended voltage supply is compatible  
with the voltage configuration indicated on the electronics and  
the external nameplate. Connect power as shown in Figure 5.  
Select wire size that can deliver suitable voltage and current for  
the application.  
Output Relay Contacts: (See Figure 5)  
The LV800 is equipped with one or two sets of isolated contacts  
which indicates whether or not material is being detected with-  
in the vessel. This output is also influenced by the selection of  
the "fail-safe" switch as described in the "Calibration" section of  
this manual. The designations on the circuit board relate to the  
contact status when the material is "not" sensed and the fail-  
safe switch is in the "low" mode. These contacts can be con-  
nected to any type of control device, provided that ratings are  
observed (See Specifications). Select wire size that can deliv-  
er suitable voltage and current for the application.  
Figure 6  
2-Step Calibration- probe exposed to free air only  
1) Rotate “Sense Adjust” clockwise just until the “Sense”  
(yellow) LED turns on.  
2) Reposition “Sense Adjust” a number of turns counter-  
clockwise with respect to the three described sensitivities  
below (see Figure 7). It is desirable to reposition “Sense  
Adjust” in accordance to “2-Step Calibration - probe  
exposed to material” procedure once material can cover the  
probe. Materials with high dielectric constants or conductiv-  
ity, require the sensitivity adjustment further counter-  
clockwise than those applications with low dielectric  
constants.  
Figure 5  
CA LIBR ATIO N  
Sensitivity: (See Figure 6)  
Sensitivity is set in the field via a "Sense Adjust" 25-turn poten-  
tiometer.  
The “Sense Adjust” tunes the sensitivity of the LV800 to the  
material being sensed. Rotating the adjustment in a clockwise  
direction will increase the sensitivity making the material easier  
to “detect”. There are two different procedures which can be  
used in the calibration process. Both utilize the simple “2-Step  
Calibration” procedure. One procedure sets the sensitivity with  
the probe being exposed to the material, while the second pro-  
cedure exposes the probe to free air only. Since the capaci-  
tance being measured is directly related to the material being  
sensed, the best results will be achieved by setting the calibra-  
tion while the probe is exposed to the application material.  
5
 
LV800  
Figure 7  
Delay:  
A potentiometer is provided for setting the time delay between  
the time material is "sensed" (Yellow LED on) and the time the  
relay contact output changes (Red LED on). Units have a 1-  
turn potentiometer. A clockwise rotation will increase the delay  
from .25 to 15 seconds. This adjustment minimizes false sig-  
nals associated with temporary material shifts. The delay  
between the time material is "not sensed" (Yellows LED off)  
and the time the relay contact output changes (Red LED off) is  
fixed at .25 seconds.  
Figure 9  
2) Red LED - Its status describes the "operate/output" condi-  
tion of the LV800. Illumination indicated the relay is in the  
"operate/material sensed" condition. Its state is influenced  
by the time delay setting but not by the fail-safe setting. This  
LED is aimed at the lens in the cover so it can be seen with  
the cover on or off.  
3) Green LED - Its status indicates “no material sensed” con-  
dition of the LV800 in combination with the time delay set-  
ting. If material has not been sensed for a long enough  
time (as set by the time delay setting), this LED will be illu-  
minated. The red and green LEDs should never be illumi-  
nated at the same time. The green LED's state is not  
affected by the fail-safe setting. This LED is also aimed at  
the lens in the cover so that it can be seen with the cover  
on or off.  
Fail-safe: (see Figure 8)  
The term fail-safe refers to the output signal condition which  
occurs with a loss of power to the probe. A switch permits  
selection of either low or high fail-safe.  
High Fail-Safe: The relay will de-energize when material  
is sensed at high level or with power loss.  
Low Fail-Safe: The relay will de-energize when material  
is below low level or with power loss. Note the designations  
on the electronics label refer to the relay contact status  
when no material is sensed and low fail-safe is selected  
(Relay is de-energized). The designations are reversed  
when no material is sensed and high fail-safe is selected  
(Relay is energized).  
Figure 8  
Indicators: (See Figure 9)  
1) Yellow LED - Its status describes the "sensing" condition of  
the LV800. Illumination indicated that the amount of capac-  
itance established by the "Sense Adjust" has been detect-  
ed. Its status is not affected by the time delay setting of the  
fail-safe setting. This LED can only be seen when the cover  
has been removed.  
6
 
TROUBLESHOOTING  
MAINTENANCE  
PROBLEM: Sensor will not sense material  
CAUSE/SOLUTION:  
1) Verify power is applied to the sensor.  
Fuse Replacement:  
The fuse incorporated into the LV800 PCB is not intended for  
operator replacement. A qualified technician can replace the  
applicable fuse according to the following specifications. If nec-  
essary, consult the factory for additional technical assistance or  
for return of the LV800.  
2) Verify "Sense Adjust." Reposition adjustment clockwise  
therefore making the probe more sensitive to "difficult to  
sense" materials.  
3) Verify probe coverage when sensing is expected. The sen-  
sor is not designed to be "tip sensitive." Permit significant  
probe coverage before expecting material sensing.  
4) Verify electrical continuity between sensor housing and ves-  
sel wall.  
115VAC  
F1: 5x20mm, 0.63A Time Lag (Slo-Blo), 250VAC  
Littelfuse:  
Bussman:  
#218.063  
#GDC-63mA  
230VAC  
F1: 5x20mm, 0.32A Time Lag (Slo-Blo), 250VAC  
5) Verify connection of the electronic module to the probe.  
Littelfuse:  
Bussman:  
#218.032  
#GDC-32mA  
PROBLEM: Sensor remains in the "SENSE" mode even  
when material is absent  
CAUSE/SOLUTION:  
Preventive Maintenance:  
1) Verify the active probe is not in direct contact with any inter-  
nal vessel structure. If so, reposition sensor.  
2) Verify "Sense Adjust" setting. Reposition adjustment  
counter-clockwise therefore making the probe less sensitive  
to "easy to sense" materials.  
3) Verify there is not a large buildup of material between the  
active probe and the probe housing. See "Cleaning" in the  
"Maintenance" section of this bulletin.  
The LV800 design is virtually maintenance free. In typical  
applications, once the sensor is properly calibrated, it will oper-  
ate without any further attention. In abrasive applications,  
probe condition should be periodically observed. Although the  
probe's construction is made with high quality engineering plas-  
tics, heavy abrasion can wear away the probe's insulators. This  
can influence the calibration and eventually lead to sensor fail-  
ure. The electronics are housed in a weatherproof enclosure.  
In addition the PCBs are conformal coated with a silicone-  
based material to further prevent electrical influence by con-  
densation. The sensor electronics should periodically be  
observed for any signs of contamination caused by improper  
enclosure protection (i.e. insure cover is fully engaged, and that  
wire entries are properly sealed.)  
PROBLEM: Sensor does not seem to hold its calibration  
CAUSE/SOLUTION:  
1) Verify that the "sense adjust" is positioned at ideal point as  
described in 2-Step Calibration procedure. Placing setting  
too close to threshold can create nuisance false signals.  
2) Maximize probe coverage of material being sensed.  
"Difficult to detect" materials (i.e. low dielectric or light mate-  
rials) are more easily detected when more probe is covered.  
Avoid setups where "probe tip sensitivity" is required.  
3) Insure electrical continuity between the probe's mounting  
point (3/4" NPT or 1 1-4" NPT) and the bin wall. Sealant  
tapes (i.e. Teflon tape) can electrically isolate these regions  
and make sensing more difficult.  
Cleaning Requirements:  
Environmental and hazardous location protection is highly  
dependent on the proper installation of the cover to the hous-  
ing. A lubricant is applied to the housing/cover threads to  
enhance ability to twist-on twist-off cover. Clean and re-lubri-  
cate threads if necessary to insure trouble-free operation. Do  
not physically alter threads in anyway otherwise environmental  
or hazardous location protection could be compromised.  
4) Assess the temperature swing that the electronics sees in  
application. Applications with "difficult to detect" materials  
and that experience a wide temperature swing are the most  
vulnerable. Consult factory for support.  
The driven shield feature of the LV800 is designed to minimize  
the need for cleaning the probe portion of the sensor. In appli-  
cations where material build-up is so excessive that electronics  
can not adequately compensate, probe cleaning may be nec-  
essary. If so, wipe the probe with a clean damp cloth from the  
housing to the probe tip.  
PROBLEM: Output contacts perform opposite of  
designations (N/O, N/C)  
CAUSE/SOLUTION:  
1) Designations on PCB relate to relay status when in "Fail-  
Safe Low" mode and when no material is sensed. If "Fail-  
safe High" mode is used, the designations are reversed.  
Swap wire terminations of N/O and N/C if necessary.  
Changing the fail-safe selection is not recommended.  
7
 
MECHANICALS  
DIMENSIONS ARE SHOWN IN INCHES WITH MILLIMETER EQUIVALENT IN BRACKETS  
Standard Probe  
Stub Probe  
8
 
SAFETY  
S P EC IFIC ATI ON S  
Power:  
115VAC ( 15%); 2.5VA; 50/60Hz / 230VAC ( 15%); 2.5VA; 50/60Hz  
6562 ft (2000 m) max  
Altitude:  
General Safety  
Installation Category: II  
Pollution Degree:  
Ambient Op Temp:  
*Internal Bin Temp:  
CAUTION: It is essential that all instructions in this manual be followed to  
ensure proper operation of the equipment and safety of operating person-  
nel. Use of equipment not specified herein, may impair protection provid-  
ed by equipment. The use of this symbol is used throughout manual to  
highlight important safety issues. Please pay particular attention to these  
items.  
4 (Reduced to 2 by enclosure) Suitable for indoor/outdoor use  
-40˚ F (-40˚ C) to +150˚ F (+65˚ C)  
To +176˚ F (+80˚ C) w/alum. mount (<104˚ F (40˚ C) ambient)  
To +400˚ F (+204˚ C) w/SS mount (<122˚ F (50˚ C) ambient)  
SPDT, 5A @ 250VAC, 30VDC maximum  
Output Relay:  
External Indicators:  
Sensitivity:  
Stability:  
Time Delay:  
Red and green LEDs indicating power and operating mode  
Multi-turn potentiometer adjustment 0.5pf to 150 pf  
0.015pf per degree F ( 0.027pf per degree C) @ 0.5pf setting  
Electrical Shock Caution  
0.25 to 15 sec delay-to-activate, adjustable  
Certain LV800 models are powered with HIGH VOLTAGE. No operator  
serviceable parts are inside. All servicing is to be performed by qualified  
personnel. Each MK-2e is provided with a "protective conductor terminal"  
which shall be terminated to earth ground potential (See Electrical  
Installation). This product's design complies with EN61010-1 installation  
category II and pollution degree 2.  
0.25 sec delay-to-deactivate, fixed  
Fail-Safe:  
Switch selectable - HI/LO  
Build-up Immunity:  
Enclosure:  
Protected via driven shield to 150 ohm load  
Cast alum screw-on cover, beige polyester pwdr coat, NEMA 4, IP66  
Two (2) 3/4” NPT connections  
Conduit Connection:  
**Approvals:  
CSAUS CSAC Ordinary Locations, CE Mark(Ordinary location only)  
Standard/Food Grade Probe  
Mounting:  
1-1/4” NPT alum or combo 3/4” NPT 316SS and 1-1/4” NPT alum  
Probe Material:  
Probe Length:  
3/8in(9.5mm) dia. 316SS probe & guard, PPS insulators  
16in(406mm) from alum mounting  
Electromagnetic Compatibility (EMC)  
The LV800 was tested and found to comply with the standards listed  
below. The LV800 should not be used in residential or commercial envi-  
ronments. Compliance to EMC standards was demonstrated by means of  
a test setup using the following installation methods.  
1) LV800 enclosure was connected to earth ground (protective  
earth).  
Temp (Probe Only): PPS+450˚ F (+232˚ C) max;  
Pressure:  
Stub Probe  
Mounting:  
50 psi(3.5 bar) max (alum connection);150 psi(10 bar) max (3/4” NPT SS)  
1-1/4” NPT alum, or combo  
3/4” NPT 316SS and 1-1/4” NPT alum  
3/8in(9.5mm) dia. 316SS probe & guard, PPS insulators  
Cut to customer specification; application dependent  
Probe Material:  
Probe Length:  
Temp (Probe Only): PPS +450˚ F (+232˚ C) max  
Pressure:  
2) No specific wiring convention was used to supply power or  
to retrieve output signal from the LV800.  
50 psi(3.5 bar) max (aluminum); 150 psi(10 bar) max (3/4 NPT SS)  
EMC Emissions:  
Meets EN 61326-1  
EN 55011  
*Influenced by mounting, material thermal conductivity and ambient temperature.  
Electrical Equipment for Control Use, EMC  
Radiated and conducted emissions  
(Class A- industrial)  
EN 61000-3  
Fluctuations/Flicker  
Meets FCC Part 15B:  
CISPR 11  
RF Devices, Unintentional Radiators  
Radiated and conducted emissions  
(Class A- industrial)  
EMC Immunity:  
Meets EN 61326-1  
Electrical Equipment for Control Use,  
EMC  
IEC 1000-4-2  
IEC 1000-4-3  
IEC 1000-4-4  
IEC 1000-4-5  
IEC 1000-4-6  
IEC 1000-4-8  
Electrostatic discharge (industrial)  
RF radiated EM fields (industrial)  
Electrical fast transients (industrial)  
Electrical surges (industrial)  
RF conducted EM energy (industrial)  
Power frequency magnetic fields  
(industrial)  
IEC 1000-4-11  
Source voltage deviation  
9
 
WARRANTY/DISCLAIMER  
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a  
period of 13 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month  
grace period to the normal one (1) year product warranty to cover handling and shipping time. This  
ensures that OMEGA’s customers receive maximum coverage on each product.  
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service  
Department will issue an Authorized Return (AR) number immediately upon phone or written request.  
Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no  
charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, includ-  
ing but not limited to mishandling, improper interfacing, operation outside of design limits,  
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of  
having been tampered with or shows evidence of having been damaged as a result of excessive corrosion;  
or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating  
conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not  
limited to contact points, fuses, and triacs.  
OMEGA is pleased to offer suggestions on the use of its various products. However,  
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any  
damages that result from the use of its products in accordance with information provided by  
OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the  
company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR  
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF  
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY  
AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF  
LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of  
OMEGA with respect to this order, whether based on contract, warranty, negligence,  
indemnification, strict liability or otherwise, shall not exceed the purchase price of the  
component upon which liability is based. In no event shall OMEGA be liable for  
consequential, incidental or special damages.  
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic  
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical  
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or  
activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility  
as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify  
OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the  
Product(s) in such a manner.  
RETURN REQUESTS/INQUIRIES  
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE  
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN  
(AR) NUMBER FROM OMEGAS CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID  
PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return  
package and on any correspondence.  
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent  
breakage in transit.  
FOR WARRANTY RETURNS, please have the  
following information available BEFORE  
contacting OMEGA:  
FOR NON-WARRANTY REPAIRS, consult OMEGA  
for current repair charges. Have the following  
information available BEFORE contacting OMEGA:  
1. Purchase Order number under which the prod-  
uct was PURCHASED,  
1. Purchase Order number to cover the COST  
of the repair,  
2. Model and serial number of the product under  
warranty, and  
3. Repair instructions and/or specific problems  
relative to the product.  
2. Model and serial number of the product, and  
3. Repair instructions and/or specific problems  
relative to the product.  
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our  
customers the latest in technology and engineering.  
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.  
© Copyright 2005 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, repro-  
duced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior  
written consent of OMEGA ENGINEERING, INC.  
10  
 
Where Do I Find Everything I Need for  
Process Measurement and Control?  
OMEGA…Of Course!  
Shop online at omega.com  
TEMPERATURE  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies  
Wire: Thermocouple, RTD & Thermistor  
Calibrators & Ice Point References  
Recorders, Controllers & Process Monitors  
ߜ
 
Infrared Pyrometers  
PRESSURE, STRAIN AND FORCE  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Transducers & Strain Gages  
Load Cells & Pressure Gages  
Displacement Transducers  
Instrumentation & Accessories  
FLOW/LEVEL  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Rotameters, Gas Mass Flowmeters & Flow Computers  
Air Velocity Indicators  
Turbine/Paddlewheel Systems  
Totalizers & Batch Controllers  
pH/CONDUCTIVITY  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
pH Electrodes, Testers & Accessories  
Benchtop/Laboratory Meters  
Controllers, Calibrators, Simulators & Pumps  
Industrial pH & Conductivity Equipment  
DATA ACQUISITION  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Data Acquisition & Engineering Software  
Communications-Based Acquisition Systems  
Plug-in Cards for Apple, IBM & Compatibles  
Datalogging Systems  
ߜ
 
Recorders, Printers & Plotters  
HEATERS  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Heating Cable  
Cartridge & Strip Heaters  
Immersion & Band Heaters  
Flexible Heaters  
ߜ
 
Laboratory Heaters  
ENVIRONMENTAL  
MONITORING AND CONTROL  
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
ߜ
 
Metering & Control Instrumentation  
Refractometers  
Pumps & Tubing  
Air, Soil & Water Monitors  
Industrial Water & Wastewater Treatment  
pH, Conductivity & Dissolved Oxygen Instruments  
M-4168/0405  
 

Miele Refrigerator 09 170 080 User Manual
Milwaukee Power Hammer 1854 1 User Manual
Network Technologies Switch ETH 4X1 2X1 User Manual
NordicTrack Treadmill NTTL18991 User Manual
NuTone Fan 668RP User Manual
OEM Systems Speaker System PLT 522G User Manual
Panasonic All in One Printer KX F880 User Manual
Panasonic Camcorder AG DVC180B User Manual
Panasonic Car Stereo System CQ C3401 User Manual
Patton electronic Marine Battery 2017P60 RS 232 to 60mA User Manual